Connect your DC power (6–24V) and the RS485 A/B lines. It is highly recommended to use shielded twisted-pair cables for RS485 to minimize interference in industrial settings. Sensor Connection:
The NT18B07 communicates via function codes 03 (Read) and 06 (Write). The default communication settings are 9600 baud rate, 8 data bits, 1 stop bit, and no parity Key Register Addresses: 0x0000 to 0x0006: Channels 1 through 7 temperature readings. 0x0008 to 0x000E: Temperature correction/offset values for each channel. nt18b07 manual
NT18B07 7-channel NTC temperature interface board * Registers 0-6 contain temperature readings in 0.1 degree celcius increments. * Read the Docs Connect your DC power (6–24V) and the RS485 A/B lines
The NT18B07 is designed for versatility, supporting both DIN rail and wall mounting. Power & RS485: 8 data bits